OS - WinCC -- Configuring Alarm Logging -- Configuring alarms and messages
How can you create operator inputs through user-specific actions in up to and including WinCC V6.0 SP4?
How do you display and operate alarms in Runtime?
What do you do if alarms are not displayed at Runtime?
How can you change the column width of the message blocks with the mouse in WinCC Alarm Control when configuring in the Graphics Designer or in Runtime?
Configuring the system block "PLC/CPU number" in messages
Why are measuring-point-specific messages not displayed in the faceplate (PCS 7 V4.x / V5.x)?
What can you do if no messages are displayed in the overview area of WinCC?
Generating a new time stamp despite identical operator messages
Triggering of the horn with messages that are blocked for specific users
Why are the time stamps of messages struck through or replaced by asterisks in PCS 7?
SIMATIC PCS 7 V5/V6 - non-acknowledgable messages on the message new page
What are the priorities for the display of faults, warnings etc. in the group display?
How can you have a block comment displayed in an operator message?
Why are operator messages shown only on the OS server and not on the OS client?
Why after upgrading from PCS 7 V6.0 SP2 to SP3 isn't the operator who acknowledges a message entered in the operator message?
Why doesn't the operator prompt flash in the group display?
Modification of the printing color in the tag logging
How can I make messages for a certain operator be displayed in WinCC Runtime but cannot be acknowledged?
How can you reconfigure the alarm acknowledgment behavior?
Why isn't the process message displayed in my PCS 7 project?
How do you suppress the process control group messages?
What is the meaning of the process control group messages created during OS compilation?
Which process control group messages are created in the OS?
What can you do if no messages are displayed in the overview area of WinCC?
Part number:

Description
Check whether one of the cases below applies.

  • In a picture, faceplates were not incorporated as OLE Control, but with the dynamic wizard "Screen selection via measuring point". In this case the messages of these faceplates are not forwarded to the group display in the overview area.
    Remedy
    Insert a group display into the picture for each faceplate. Link the "Group Value" property of each group display directly to the EventState tag of the measuring points that are connected to the faceplates. You can switch the group display to be hidden by way of the "View" property. Save the "Picture Tree Manager" to complete configuration of the group displays.
     
  • The messages from pictures that are at a lower level than others in the "Picture Tree Manager" are not put through to the next highest level automatically.
    Remedy
    Place a group display in the higher level picture. Link the group display with the lower level picture using the dynamic wizard "Link group display with picture". You can switch the group display to be hidden by way of the "View" property. Save the "Picture Tree Manager" to complete configuration of the group displays.
     
  • If you have inserted faceplates or group displays into a picture, their messages are displayed in the overview area only if the "Picture Tree Manager" has been saved.
    Remedy
    Deactivate WinCC and open the "Picture Tree Manager". In the "Tools" menu you must enable the "Recalculate entire group display hierarchy when saving" option. Now save the "Picture Tree Manager". If there are still no messages displayed in the overview area, close and re-open WinCC.
 Entry ID:674987   Date:2011-02-24 