Product Notes This entry contains all the SIMATIC HMI panels, panel PCs and flat screens that Siemens is currently offering for hazardous areas with potentially explosive atmosphere (Ex2/22).
Contents
1. HMI Panels, Panel PCs and Flat Screens with Explosion Protection 22 ("Dust Ex")
2. HMI Panels and Flat Screens with Explosion Protection 2 ("Gas Ex")
3. Information about Explosion Protection 1
4. Download
Pay attention to the explosion protection ID on the back of the device before installing the panel. Panels mentioned in the certificate should not be used automatically in the hazardous areas with potentially explosive atmosphere. What counts here is the ID on the back of the device.

Fig. 01 - ID for explosion protection
1. Explosion protection 22
The following panels, panel PCs and flat screens are tested according to Explosion Protection Zone 22 ("Dust Ex") in compliance with the ATEX Cat. II 3 D (authorization in compliance with EN 60079-15/EN 50281-1-1).
These devices include:
| Key Panels |
MLFB |
Certificate |
| German |
English |
KP8
(as from "E-Stand 03") |
6AV3688-3AY36-xxxx |
24038945 |
22642669 |
KP8F
(as from "E-Stand 03") |
6AV3688-3AY37-xxxx |
24038945 |
22642669 |
| Micro Panels |
MLFB |
Certificate |
| German |
English |
TP 177micro
(as from "E-Stand" 18) |
6AV6640-0CA11-xxxx |
24038945 |
22642669 |
| Operator Panels |
MLFB |
Certificate |
| German |
English |
OP 77A
(as from "E-Stand" 13) |
6AV6641-0BA11-xxxx |
24038945 |
22642669 |
OP 77B
(as from "E-Stand" 11) |
6AV6641-0CA01-xxxx |
24038945 |
22642669 |
OP 177B DP
(as from "E-Stand" 14) |
6AV6642-0DC01-xxxx |
24038945 |
22642669 |
OP 177B PN/DP
(as from "E-Stand" 14) |
6AV6642-0DA01-xxxx |
24038945 |
22642669 |
| Touch Panels |
MLFB |
Certificate |
| German |
English |
TP 177A
(as from "E-Stand" 16) |
6AV6642-0AA11-xxxx |
24038945 |
22642669 |
TP 177B DP mono
(as from "E-Stand" 14) |
6AV6642-0BC01-xxxx |
24038945 |
22642669 |
TP 177B PN color
(as from "E-Stand" 14) |
6AV6642-0BA01-xxxx |
24038945 |
22642669 |
| TP 177B INOX |
6AV6642-8BA10-xxxx |
24038945 |
22642669 |
TP 277 6"
(as from "E-Stand" 06) |
6AV6643-0AA01-xxxx |
24462135 |
24462792 |
| Multi Panels |
MLFB |
Certificate |
| German |
English |
MP 277 8" Touch
(as from "E-Stand" 04) |
6AV6643-0CB01-xxxx |
24462135 |
24462792 |
MP 277 10" Key
(as from "E-Stand" 04) |
6AV6643-0DD01-xxxx |
24462135 |
24462792 |
MP 277 10" Touch
(as from "E-Stand" 04) |
6AV6643-0CD01-xxxx |
24462135 |
24462792 |
| MP 277 10" Touch INOX Ex (as from "E-Stand" 02) |
6AV6643-0ED01-xxxx |
19237714 |
31596568 |
| MP 277 10" Touch INOX |
6AV6643-84D10-xxxx |
24462135 |
24462792 |
MP 377 12" Touch
(as from "E-Stand" 04) |
6AV6644-0AA01-xxxx |
24462135 |
24462792 |
MP 377 12" Key
(as from "E-Stand" 03) |
6AV6644-0BA01-xxxx |
24462135 |
24462792 |
MP 377 15" Touch
(as from "E-Stand" 03) |
6AV6644-0AB01-xxxx |
24462135 |
24462792 |
| MP 377 INOX 15" Touch (as from "E-Stand" 02) |
6AV6644-0CB01-xxxx |
18336077 |
15227494 |
| MP 377 15" Daylight |
6AV6644-8AB20-xxxx |
18336077 |
15227494 |
| MP 377 19" Touch |
6AV6644-0AC01-xxxx |
24462135 |
24462792 |
| Comfort Panels |
MLFB |
Certificate |
| German |
English |
| KTP400 Comfort |
6AV2124-2DC01-0AX0 |
Yes |
Yes |
| KP400 Comfort |
6AV2124-1DC01-0AX0 |
In preparation |
In preparation |
| TP700 Comfort |
6AV2124-0GC01-0AX0 |
Yes |
Yes |
| KP700 Comfort |
6AV2124-1GC01-0AX0 |
Yes |
Yes |
| TP900 Comfort |
6AV2124-0JC01-0AX0 |
Yes |
Yes |
| KP900 Comfort |
6AV2124-1JC01-0AX0 |
In preparation |
In preparation |
| TP1200 Comfort |
6AV2124-0MC01-0AX0 |
Yes |
Yes |
| KP1200 Comfort |
6AV2124-1MC01-0AX0 |
Yes |
Yes |
| TP1500 Comfort |
6AV2124-0QC02-0AX0 |
In preparation |
In preparation |
| KP1500 Comfort |
6AV2124-1QC02-0AX0 |
In preparation |
In preparation |
| TP1900 Comfort |
6AV2124-0UC02-0AX0 |
In preparation |
In preparation |
| TP2200 Comfort |
6AV2124-0XC02-0AX0 |
In preparation |
In preparation |
Flat Panel monitor
extended |
MLFB |
Certificate |
| 17" Monitor 24V |
6AV7861-4AB10-xxxx |
31898107 |
| 17" Monitor 24V |
6AV7861-4AA00-xxxx |
31898107 |
| 17" Monitor 230V |
6AV7861-4AB00-xxxx |
31898107 |
| 17" Touch 24V |
6AV7861-4TB10-xxxx |
31898107 |
| 17" Touch 24V |
6AV7861-4TA00-xxxx |
31898107 |
| 17" Touch 230V |
6AV7861-4TB00-xxxx |
31898107 |
| 19" Monitor 24V |
6AV7861-3AB10-xxxx |
31898107 |
| 19" Monitor 24V |
6AV7861-3AA00-xxxx |
31898107 |
| 19" Monitor 230V |
6AV7861-3AB00-xxxx |
31898107 |
| 19" Touch 24V |
6AV7861-3TB10-xxxx |
31898107 |
| 19" Touch 24V |
6AV7861-3TA00-xxxx |
31898107 |
| 19" Touch 230V |
6AV7861-3TB00-xxxx |
31898107 |
| SIMATIC IPC |
MLFB |
Certificate |
| German |
English |
| SIMATIC HMI IPC677C |
6AV7894-... |
51546529 |
51546508 |
| SIMATIC HMI |
MLFB |
Certificate |
| German |
English |
| SIMATIC HMI Panel PC Ex |
6AV7200-1Axxx-xxA0
6AV7200-1Bxxx-xxA0 |
43527040 |
43527040 |
| SIMATIC HMI Thin Client Ex |
6AV7200-0Ax00-xxA0
6AV7200-0Bx00-xxA0 |
43526280 |
43526280 |
Table 01
2. Explosion protection 2 The following panels are tested according to Explosion Protection Zone 2 ("Gas Ex") in compliance with the ATEX Cat. II 3 G (authorization in compliance with EN 60079-15/EN 50281-1-1).
These panels include:
|
Key Panels |
MLFB |
Certificate |
| German |
English |
KP8
(as from "E-Stand 03") |
6AV3688-3AY36-xxxx |
24038945 |
22642669 |
KP8F
(as from "E-Stand 03") |
6AV3688-3AY37-xxxx |
24038945 |
22642669 |
| Micro Panels |
MLFB |
Certificate |
| German |
English |
TP 177micro
(as from "E-Stand" 18) |
6AV6640-0CA11-xxxx |
24038945 |
22642669 |
| Operator Panels |
MLFB |
Certificate |
| German |
English |
OP 77A
(as from "E-Stand" 13) |
6AV6641-0BA11-xxxx |
24038945 |
22642669 |
OP 77B
(as from "E-Stand" 11) |
6AV6641-0CA01-xxxx |
24038945 |
22642669 |
OP 177B DP
(as from "E-Stand" 14) |
6AV6642-0DC01-xxxx |
24038945 |
22642669 |
OP 177B PN/DP
(as from "E-Stand" 14) |
6AV6642-0DA01-xxxx |
24038945 |
22642669 |
|
Touch Panels |
MLFB |
Certificate |
| German |
English |
TP 177A
(as from "E-Stand" 16) |
6AV6642-0AA11-xxxx |
24038945 |
22642669 |
TP 177B DP mono
(as from "E-Stand" 14) |
6AV6642-0BC01-xxxx |
24038945 |
22642669 |
TP 177B PN/DP color
(as from "E-Stand" 14) |
6AV6642-0BA01-xxxx |
24038945 |
22642669 |
| TP 177B PN/DP color INOX |
6AV6642-8BA10-xxxx |
24038945 |
22642669 |
| Multi Panels |
MLFB |
Certificate |
| German |
English |
| MP 277 10" Touch INOX (as from "E-Stand" 02) |
6AV6643-0ED01-xxxx |
19237714 |
31596568 |
| MP 377 15" Touch INOX (as from "E-Stand" 02) |
6AV6644-0CB01-xxxx |
18336077 |
15227494 |
| MP 377 15" Touch Daylight |
6AV6644-8AB20-xxxx |
18336077 |
15227494 |
| Comfort Panels |
MLFB |
Certificate |
| German |
English |
| KTP400 Comfort |
6AV2124-2DC01-0AX0 |
Yes |
Yes |
| KP400 Comfort |
6AV2124-1DC01-0AX0 |
In preparation |
In preparation |
| TP700 Comfort |
6AV2124-0GC01-0AX0 |
Yes |
Yes |
| KP700 Comfort |
6AV2124-1GC01-0AX0 |
Yes |
Yes |
| TP900 Comfort |
6AV2124-0JC01-0AX0 |
Yes |
Yes |
| KP900 Comfort |
6AV2124-1JC01-0AX0 |
In preparation |
In preparation |
| TP1200 Comfort |
6AV2124-0MC01-0AX0 |
Yes |
Yes |
| KP1200 Comfort |
6AV2124-1MC01-0AX0 |
Yes |
Yes |
| TP1500 Comfort |
6AV2124-0QC02-0AX0 |
In preparation |
In preparation |
| KP1500 Comfort |
6AV2124-1QC02-0AX0 |
In preparation |
In preparation |
| TP1900 Comfort |
6AV2124-0UC02-0AX0 |
In preparation |
In preparation |
| TP2200 Comfort |
6AV2124-0XC02-0AX0 |
In preparation |
In preparation |
| SIMATIC HMI |
MLFB |
Certificate |
| German |
English |
| SIMATIC HMI Panel PC Explosion Protection Zone 2 |
6AV7200-1Axxx-xxA0
6AV7200-1Bxxx-xxA0 |
43527040 |
43527040 |
| SIMATIC HMI Thin Client |
6AV7200-0Ax00-xxA0
6AV7200-0Bx00-xxA0 |
43526280 |
43526280 |
Table 02
We do not currently offer Flat Panel monitors in accordance with Explosion Protection Zone 2 ("Gas Ex") in compliance with ATEX Cat. II 3 G (authorization in compliance with EN 60079-15/EN 50281-1-1).
If you have a device for the Ex protection class 1 (Cat. II 2 G/D), then please get in touch with your sales partner.
3. Explosion protection 1
| SIMATIC HMI |
MLFB |
Certificate |
| German |
English |
| SIMATIC HMI Panel PC Explosion Protection Zone 1 |
6AV7200-1Dxxx-xxA0
6AV7200-1Exxx-xxA0
6AV7200-1Fxxx-xxA0 |
43526495 |
43526495 |
| SIMATIC HMI Thin Client |
6AV7200-0Dx00-xxA0
6AV7200-0Ex00-xxA0
6AV7200-0Fx00-xxA0 |
43526280 |
43526280 |
Table 03
Note Certifications are available from your regional Siemens sales partner or in the Internet at the following link:
http://support.automation.siemens.com/WW/view/en/10805558/134200.
4. Download
The attachment below contains information on the conditions for Zones 2 and 22, as well as information on the certification and repair of the various operator panels.
Attachment: PI_ATEX_Release_03-2009.zip ( 3700 KB )
Remark
Also note the following entry with Entry ID: 29386622 about the loss of Ex approval of the panels TD100/200, OP7, TD17, OP17, OP77, xP177 and xP270 6" on 01.06.2008.
Additional Keywords Ex area, Ex zone, Protection class, Explosion protection
|