Interface assignment of the cable types: The operator panels can communicate with many different controllers. For this you need different cables and cable types. The tables below give you an overview of the types of communication and the cables that can be used.
Controller connections:
- SIMATIC S5
- SIMATIC 500/505
- Mitsubishi FX
- Telemecanique Uni-Telway
- Allen Bradley
- Omron
- FANUC
- Modicon Modbus
Special connections:
- TD390 to S5
- Zero modem cable for Active Sync
- OP and PG/PC simultaneously to MPI
Miscellaneous:
The list below contains only the most important connecting cables. More cables are listed in the manuals. Please not that some products listed here are discontinued and thus you cannot order them anymore. More information on the discontinuation of the products concerned is available in Entry ID: 23486974.
1. SIMATIC S5 Cables for connecting an operator panel to SIMATIC S5
| No. |
Cable type / Special features |
|
1 |
Operator panel - SIMATIC S5 with AS 511 |
6XV1440-2A...
  Bild 01 |
| TTY |
|
Connector 1:
15-pin Sub-D male connector
Connector 2:
15-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 1000m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006
Note: For TTY cable with special lengths > 10m, you must solder 2 Zener diodes (12V) in the 15-pin connector to the operator panel (TTY active). |
|
2 |
Operator panel - CP 521 SI |
6XV1440-2G...
  Bild 02 |
| TTY |
Connector 1:
15-pin Sub-D male connector
Connector 2:
25-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 1000m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006
Note: For TTY cable with special lengths > 10m, you must solder 2 Zener diodes (12V) in the 15-pin connector to the operator panel (TTY active). |
|
3 |
Operator panel - CP 523 |
6XV1440-2F...
  Bild 03 |
| TTY |
Connector 1:
15-pin Sub-D male connector
Connector 2:
15-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 1000m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006
Note: For TTY cable with special lengths > 10m, you must solder 2 Zener diodes (12V) in the 15-pin connector to the operator panel (TTY active). |
|
4 |
Operator panel - CPU 928B/945 |
6XV1440-2J...
  Bild 04 |
| TTY |
|
Connector 1:
15-pin Sub-D male connector
Connector 2:
25-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 1000m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
More cable connections to the SIMATIC S5 are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > SIMATIC S5 > Connection cables for SIMATIC S5".
back
2. SIMATIC 500/505 Cables for connecting an operator panel to SIMATIC TI
| No. |
Cable type / Special features |
|
1 |
Operator panel - SIMATIC 505 |
6XV1440-1M...
  Bild 05 |
| RS422 |
Connector 1:
9-pin Sub-D male connector
Connector 2:
9-pin Sub-D female connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 300m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
2 |
Operator panel - SIMATIC 500/505 |
6XV1440-2K...
  Bild 06 |
| V.24 |
Connector 1:
15-pin Sub-D male connector
Connector 2:
9-pin Sub-D female connector
Cable:
5 x 0.14mm², shielded, max. length 15m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
3 |
Operator panel - SIMATIC 500/505 |
6XV1440-2L...
  Bild 07 |
| V.24 |
Connector 1:
15-pin Sub-D male connector
Connector 2:
25-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 15m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
4 |
Operator panel - SIMATIC 500/505 |
6XV1440-2M...
  Bild 08 |
| RS422 |
Connector 1:
9-pin Sub-D male connector
Connector 2:
9-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 300m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
5 |
Operator panel RS422 - SIMATIC 500/505 RS422 |
6XV1440-2N...
  Bild 09 |
| RS422 |
Connector 1:
25-pin Sub-D male connector
Connector 2:
9-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 300m
Connect shield to housing on both sides over a wide area
Note:
Valid for the following CPUs only:
TD10, TD20, OP20, OP30
Status: Discontinued since 01.10.2006 |
More cable connections to the SIMATIC 500/505 are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > SIMATIC 500/505 > Connection cables for SIMATIC 500/505".
back
3. Mitsubishi Cables for connecting an operator panel to Mitsubishi
| No. |
Cable type / Special features |
|
1 |
Operator panel - Mitsubishi Electric controller |
6XV1440-2P...
  Bild 10 |
| RS422 |
Connector 1:
9-pin Sub-D male connector
Connector 2:
8-pin Mini DIN male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 500m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
2 |
Operator panel - Mitsubishi Electric controller |
6XV1440-2Q...
  Bild 11 |
| RS422 |
Connector 1:
25-pin Sub-D male connector
Connector 2:
8-pin Mini DIN male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 500m
Connect shield to housing on both sides over a wide area
Status: discontinued |
|
3 |
Operator panel - Mitsubishi Electric controller |
6XV1440-2R...
  Bild 12 |
| RS422 |
Connector 1:
9-pin Sub-D male connector
Connector 2:
25-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 500m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
|
4 |
Operator panel - Mitsubishi FX |
6XV1440-2S...
  Bild 13 |
| RS422 |
Connector 1:
25-pin Sub-D male connector
Connector 2:
25-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 500m
Connect shield to housing on both sides over a wide area
Status: Discontinued since 01.10.2006 |
More cable connections to the Mitsubishi MELSEC are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > Mitsubishi MELSEC > Connection cables for Mitsubishi".
back
4. Telemecanique Uni-Telway Cables for connecting an operator panel to Telemecanique
More cable connections to the Telemecanique are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > Telemecanique Uni-Telway > Connection cables for Telemecanique bus".
back
5. Allen Bradley PLC-5 Cables for connecting an operator panel to Allen Bradley PLC-5
More cable connections to the Allen Bradley are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > Allen Bradley > Connection cables for Allen Bradley".
back
6. Omron Cables for connecting an operator panel to Omron
| No. |
Cable type / Special features |
|
1 |
Operator panel - Omron |
6XV1440-2X...
  Bild 19 |
| V.24 |
Connector 1:
15-pin Sub-D male connector
Connector 2:
9-pin Sub-D male connector
Cable:
5 x 0.14mm², shielded, max. length 15m
Connect shield to housing on both sides over a wide area. |
|
2 |
Operator panel - Omron |
  Bild 20 |
|
RS422 |
Connector 1:
9-pin Sub-D male connector
Connector 2:
9-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm², shielded, max. length 500m
Connect the shield contacts on both sides. |
More cable connections to the Omron are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > Omron > Connection cables for Omron Hostlink/Multilink".
back
7. Fanuc Cables for connecting an operator panel to a Fanuc controller
| No. |
Cable type / Special features |
|
1 |
Operator panel - GE Fanuc controller |
  Bild 21 |
| Multiple-point cable 1 |
|
Connector 1:
9-pin Sub-D male connector
Connector 2:
15-pin Sub-D male connector
Cable:
3 x 2 x 0.14mm, shielded, max. length 1200m
Connect shield to housing on both sides over a wide area, connect the shield contacts
Terminator:
Insert terminator R = 120 Ohm (e.g. type 0207) |
More cable connections to the Fanuc are available in the WinCC flexible Information System under "WinCC flexible Information > Communication > GE Fanuc > Connection cables for GE Fanuc".
back
8. Modicon Modbus
Cable connections to the Modicon Modbus are available in the manuals or in the WinCC flexible Information System under "WinCC flexible Information System > Communication > Modicon Modbus > Connection cables for Modicon Modbus > Connection cables for Modbus RTU protocol".
back
9. Special connections - SIMATIC S5 Cables for connecting a TD390 to an S5
| No. |
Cable type / Special features |
|
1 |
Operator panel - SIMATIC S5 |
  Bild 22 |
| TTY |
Connector 1:
9-pin Sub-D female connector
Connector 2:
15-pin Sub-D male connector |
back
10. Special connections - MS Active Sync Zero modem cable for communication between MS Active Sync and MP 270 and MP 370
| No. |
Cable type / Special features |
|
1 |
  Bild 23
|
| RS232 |
|
Connector 1:
9-pin Sub-D female connector
Connector 2:
9-pin Sub-D female connector |
back
11. Special connections - SIMATIC S7 OP and PG/PC simultaneously to an MPI interface of the S7
| No. |
Cable type / Special features |
|
1
|
RS485
Bus cable:
6XV1830-1EH10
CPU plug with PG socket:
6ES7972-0BB11-0XA0 (90-degree cable exit)
6ES7972-0BB40-0XA0 (35-degree cable exit)
6ES7972-0BB50-0XA0 (90-degree cable exit, Fast Connect)
OP connector:
6GK1500-0EA02 (180-degree cable exit)
The CPU connector and the OP connector are wired with the bus cable and connected to both devices. Now you can connect the PG to the PG socket connector of the connector on the CPU side. See also Entry ID 1070096. |
back
Note: Only the beginning of the order number is displayed in each case in the table, because the type of cable is coded. The length is coded in the digits not shown at the back.
Angular adapters: The angular adapter (9-pin) forwards all the signals in pin-compatible form. The RS422/RS232 converter (9-pin) is for connecting third-party PLCs to a panel that needs an RS232 physical. When using the converter of the RS422, you must set the RS422 interface in the configuration tool. The adapter implements the signals purely physically outside the panel.
More information on angular adapters is available in Entry ID 22150270 and in the following PDF document:
RS 422 - RS 232 Converter.pdf ( 174 KB )
Links: More connection options and interface descriptions are also available in the following manuals on communication.
| Manual |
Edition |
Entry ID |
| Graphics and text-based OPs |
05/99 |
1137086 |
| Windows-based devices |
09/00 |
1145110 |
SIMATIC HMI
Communication for Windows-based System User Manual Part 1 |
12/01 |
1405528 |
SIMATIC HMI
Communication for Windows-based System User Manual Part 2 |
12/01 |
11165960 |
back
Keywords:
Third-party controllers, Coding
|