CS 275 -- Questions to Redundancy and Bus Couplers
Settings for the X2 jumpers on the UI-SV module, release 4
What is the procedure to test the fine protection on the remote bus connector board?
Can the CS 275 capacity of transporting be reduced on the intact bus B?
It is possible that the bus redundancy is intact although an error message signals loss of the bus redundancy?
Can the bus coupler subrack BK-NF only be used at TELEPERM M, and the subrack BK-FF only at TELEPERM ME?
Have the bus couplers to be switched off before changing the bus topology from „Line“ to „Head bus“, or rearranging a bus to another position in the bus topology?
Has any sequence to be observed when switching on bus couplers in a mixed configuration?
Can telegrams partially be routed faulty with intact bus coupler?
Can telegrams partially be routed faulty with intact bus coupler?
Part number:

QUESTION:
Can telegrams partially be routed faulty with intact bus coupler?

ANSWER:
If three or more busses are connected via bus coupler units, and on (at least) one bus coupler unit the station addresses of both bus coupler modules are set equal, the following behaviour may happen:

Telegrams running through (at least) two bus coupler units are routed faulty or don't reach their target destination.
Telegrams between two neighbouring busses are not affected.

Remedy:
Both station adresses of the bus coupler modules belonging to one bus coupler unit should be set unequal.

 Entry ID:25219885   Date:2007-03-30 