show the entry list
3RW30 Soft Starter: Why does contact 13/14 not close after the start signal?
Part number:

QUESTION:
Why does relay contact 13/14 not close after the start signal?

 

 

ANSWER:

If no motor is connected on the Soft Starter 3RW30, the relay contacts 13/14 and 23/24 cannot close. These contacts can only close if a motor is connected.

 

 Entry ID:21655654   Date:2012-03-01 