QUESTION:
Is there a way of resetting the TD200C to the standard settings
(standard menu and standard keyboard)?
ANSWER:
Execute the following statements to reset the TD200C temporarily
to the standard settings (standard TD200 keyboard).
- Switch the TD200C off.
- Press and hold the key in the bottom right corner (the key for
the standard ENTER function on the standard keyboard).
- Switch the TD200C on.
Fig. 1: TD200C
The standard keyboard is restored on the TD200C for as long as
the TD200C remains switched on. When you turn the TD200C off and
then back on again, the original configuration is loaded.
|