show the entry list
Network transitions and links (DP) -- Setting up and parameterizing hardware -- Initializing and parameterizing modules
How do you link the AS-i Slaves to an S7-300 CPU with integrated PROFINET interface using the IE/AS-i Link?
Where can you find sample S7 programs and documentation for communication via PROFINET on the SIMATIC NET Quick Start Collection?
Where can you find sample S7 programs and documentation for communication in the IWLAN in the SIMATIC NET Quick Start Collection?
Where can you find sample S7 programs and documentation for communication via PROFIBUS in the SIMATIC NET Quick Start Collection?
Where can you find sample programs and documentation for communication between a PC station and SIMATIC S7 via PROFIBUS using S7 Communication and incorporating an IE/PB Link gateway?
Where do you find sample programs and documentation on communication between S7-400 (PROFINET IO controller) and S7-300 (I slave) incorporating an IE-to-PB link gateway?
Where can you find sample programs and documentation for communication between a PC station and SIMATIC S7 using S7 communication and incorporating an IE/PB link gateway?
Routing of S7 and of Data Sets (PROFIBUS DP) via the Link Gateway IE/PB
How do you configure a ring redundancy with FDC 157-0 DP/PA couplers and active field distributors (AFDs)?
Connecting an S7-300 to a DP/PA-Link
Which options do you have for accessing PROFIBUS devices from a PC behind an IWLAN/PB link PN IO or an IE/PB link PN IO?
How do you connect the IM 157/IM 153-2 in the DP/PA Link to an external master or a SIMATIC S5?(GSD-Tool)
Incorporating new LINK modules in PCS7 V4.02
Set-up restrictions when using universal modules
Reduced user data capacity when using the diagnostics
Reading the input data of a DP slave configured by a different DP master
How do you configure an S7-300 CPU or a CP342-5 as DP slave to an S7-400H as DP master using a Y-link?
Configuration of the I/O Data on DP/DP Coupler
Retrieve Diagnostics of the DP/AS-i Link 20E
Configuring I/O addresses with DP/AS-i Link 20E
What are the special features of input/output addressing with the DP/DP coupler?
Retrieve Diagnostics of the DP/AS-i Link 20E
Part number:

QUESTION:  
What do I have to observe in order to retrieve the producer-related diagnostics of the DP/AS-i Link 20E?

ANSWER:
In order to be able to retrieve the producer-related diagnostic out of the DP/AS-i Link 20E - with e. g. the SFC 13 "DP_DIAG" or  the SFB 54 "RALRM" in mode DPV1 - the option "Diagnostic Interrupt" must be activated in operation parameters.

Parametrize diagnostic setting of the DP/AS-i Link 20E as follows:

Fig. 1: Configuration of the DP/AS-i Link 20E in the Hardware Catalogue of HWConfig

Fig. 2: Configuration of the DP/AS-i Link 20E by means of DPV0-GSD File

Fig. 3: Configuration of the DP/AS-i Link 20E by means of DPV1-GSD File


 Entry ID:18848302   Date:2004-04-27 