QUESTION:
What do I have to observe in order to retrieve the
producer-related diagnostics of the DP/AS-i Link 20E?
ANSWER: In order to be able to retrieve the
producer-related diagnostic out of the DP/AS-i Link 20E - with e.
g. the SFC 13 "DP_DIAG" or the SFB 54 "RALRM" in mode DPV1 -
the option "Diagnostic Interrupt" must be activated in operation
parameters.
Parametrize diagnostic setting of the DP/AS-i Link 20E as
follows:
Fig. 1: Configuration of the DP/AS-i Link 20E in the Hardware
Catalogue of HWConfig
Fig. 2: Configuration of the DP/AS-i Link 20E by means of
DPV0-GSD File
Fig. 3: Configuration of the DP/AS-i Link 20E by means of
DPV1-GSD File
|