QUESTION:
A quel moment apparaît le message "Message overflow detected"?
REPONSE:
On trouve plusieurs inscriptions du type suivant dans le fichier
"WinCC_Sys_0x.log" (extrait d'un fichier log):
03.08.1999,11:09:45:105,1000200,4,ES1,,WinCC-Runtime,Connection
ProgrammAS1(1)#01 established
03.08.1999,11:09:45:195,1000200,4,ES1,,WinCC-Runtime,Connection
ProgrammAS2(1)#02 established
04.08.1999,10:05:03:482,1003082,4,ES1,Administrator,NRMS7PMC,MldReceiveMsg:
RDFT_EVT_PMC_ALARM8/_ALARM_T Connection ProgrammAS1(1)#01, EV_ID
0x00000086: Message overflow detected
04.08.1999,10:05:03:893,1003082,4,ES1,Administrator,NRMS7PMC,MldReceiveMsg:
RDFT_EVT_PMC_ALARM8/_ALARM_T Connection ProgrammAS1(1)#01, EV_ID
0x0000006A: Message overflow detected
04.08.1999,10:05:07:167,1003082,4,ES1,Administrator,NRMS7PMC,MldReceiveMsg:
RDFT_EVT_PMC_ALARM8/_ALARM_T Connection ProgrammAS1(1)#01, EV_ID
0x0000006C: Message overflow detected
04.08.1999,10:05:07:267,1003082,4,ES1,Administrator,NRMS7PMC,MldReceiveMsg:
RDFT_EVT_PMC_ALARM8/_ALARM_T Connection ProgrammAS1(1)#01, EV_ID
0x0000006A: Message overflow detected
La liaison avec l'ASen est d'abord établie puis des messages
sont affichés avec le message d'erreur " Message overflow
detected".
Arrière-plan:
Les blocs Alarm-8P ne peuvent stocker que 3 états (arrivé, parti,
acquitté). Si WinCC n'est pas en Runtime et que les alarmes
changent d'états plusieurs fois alors les blocs correspondants ne
peuvent transmettre ces changements d'états à WinCC. Lorsque vous
relancez le Runtime de WinCC, les blocs envoient alors toutes ces
alarmes.
Mots-clefs:
Service
|