Application area of SIPLUS extreme components:
| environmental conditions |
air pressure
1.080...795 hPa (-1.000 to +2.000m) no derating
795...658 hPa (+2.000 to +3.500m) derating 10 K of the maximum upper operating temperature
658...540 hPa (+3.500 to +5.000m) derating 20 K of the maximum upper operating temperature |
For information of the SIPLUS products go to: www.siemens.com/siplus-extreme
For further questions, please contact your Siemens-branch office.